Appendix C: Device Data Format
Siemens Energy & Automation, Inc. 95
50HS-Phase high-set element
TRIP
43 ms since fault (-1 = no occurrence)
50-Phase inst. element TRIP 44 ms since fault (-1 = no occurrence)
51-Phase time element TRIP 45 ms since fault (-1 = no occurrence)
50NHS-Ground high-set
element TRIP
46 ms since fault (-1 = no occurrence)
50N-Ground inst. element
TRIP
47 ms since fault (-1 = no occurrence)
51N-Ground time element
TRIP
48 ms since fault (-1 = no occurrence)
67-Dir. phase inst. element
TRIP
49 ms since fault (-1 = no occurrence)
67T-Dir. phase time element
TRIP
50 ms since fault (-1 = no occurrence)
67N-Dir. ground inst. element
TRIP
51 ms since fault (-1 = no occurrence)
67NT-Dir. ground time element
TRIP
52 ms since fault (-1 = no occurrence)
Dir. O/C protection PICKUP 53 ms since fault (-1 = no occurrence)
Dir. O/C protection TRIP 54 ms since fault (-1 = no occurrence)
79 -A/R cycle successful 55 ms since fault (-1 = no occurrence)
46-Negative seq. protection
TRIP
56 ms since fault (-1 = no occurrence)
27-1 Undervoltage first step
TRIP
57 ms since fault (-1 = no occurrence)
27-2 Undervoltage second
step TRIP
59 ms since fault (-1 = no occurrence)
59-Overvoltage TRIP 59 ms since fault (-1 = no occurrence)
Reserved 60–63 For future expansion
1. Status information for each parameter is transmitted in two bits. The status bit indicates status (true = 1, false = 0) for the parameter
and the valid bit indicates that the device has successfully updated the value in the status bit (true = 1, false = 0).
Device Command Data Retrieved From PLC (7SJ512)
First Command Word (Command Word) Additional Command Words (Data or Value)
0 = No command Unused
1 = Time Sync 2nd Word: Time [ms] - (0-59999)
3rd Word: Time [h/m] - high byte: HH (1-24), low byte: MM (0-59)
4th Word: Date [m/d] - high byte: MM (1-12), low byte: DD (1-31)
5th Word: Date [y] - YY (00-99)
2 = Reset LEDs Unused
3 = Activate Parameter Set A Unused
4 = Activate Parameter Set B Unused
5 = Activate Parameter Set C Unused
6 = Activate Parameter Set D Unused
10 = General Command 2nd Word: [Typ] in high byte, [Inf] in low byte
Real-Time Device Data Stored in PLC (7SJ512) (Continued)
Function Register Location in
PLC Block
Range or Contents