Appendix C: Device Data Format
64 Siemens Energy & Automation, Inc.
C.6 Device Type: SensiTrip III
Note: No Commands from this device are supported.
Real-Time Device Data Stored in PLC (SensiTrip III)
Real-Time Data Register Offset Range or Contents
MT Status 0 2 Byte ASCII string
Zone Interlock Status 1 High Order Byte: Ground Fault Zone
Low Order Byte: Short Time Zone
Device Type 2 00h = No Device
01h = MCCB/ICCB
02h = STIIIC/CP
Phase A Current (Gain Off) 3 0...65535 (must be scaled)
Phase B Current (Gain Off) 4 0...65535 (must be scaled)
Phase C Current (Gain Off) 5 0...65535 (must be scaled)
Ground Fault Current (Gain Off) 6 0...65535 (must be scaled)
Phase A Current (Gain On) 7 0...65535 (must be scaled)
Phase B Current (Gain On) 8 0...65535 (must be scaled)
Phase C Current (Gain On) 9 0...65535 (must be scaled)
Ground Fault Current (Gain On) 10 0...65535 (must be scaled)
Reserved 11-13 For Future Expansion
Breaker Status 14 2 Byte ASCII string
Configuration Switch 15 Switch setting (0...255)
Continuous Current Switch 16 Switch setting (0...255)
Long Time Delay Switch 17 Switch setting (0...255)
Instantaneous Pickup Switch 18 Switch setting (0...255)
Short Time Pickup Switch 19 Switch setting (0...255)
Short Time Delay Switch 20 Switch setting (0...255)
Ground Fault Pickup Switch 21 Switch setting (0...255)
Ground Fault Delay Switch 22 Switch setting (0...255)
Trip Unit Frame Type Code 23 ASCII character code
MCCB Types: J, L, M, N, P
SB Types: S
Trip Unit Frame Rating Code 24 2 Byte ASCII string
Display Module Type 25 00h = None
01h = Load Monitor
02h = Ground Fault Monitor
Display Module Switch 26 Switch setting (00...09)
MTA Software Version 27 0100h-0999h (0100h=Version 1.00)
Device Software Version 28 0100h-0999h (0100h=Version 1.00)
Reserved 29-33 For Future Expansion