4 Creating Project Files — Profibus to Devices
16 Siemens Energy & Automation, Inc.
2 Wire RS422 or RS485 Communications
Check this box only if the communications with your
SEAbus devices use a 2-wire RS485 or RS422 inter-
face (see Figure 4.5). This is the usual method of
connecting SEAbus devices. When 2-wire commu-
nications are being used, RTS must be looped back
to CTS on the DTU side of the cable. This can be
done on the RS232 side by looping pins 4 and 5 or
on the RS422/485 side by looping pins 16 to 18 and
17 to 19.
The remaining configuration selections, except for
intermessage time-out, are the same as those for
Port 1. Refer to Section 4.3 for instructions on these
fields.
Intermessage Time-Out
The DTU3005P uses the intermessage time-out
option to provide slave devices enough time to
respond. When a SEAbus message is received in
Port 3, a timer starts and keeps timing until the SEA-
bus device responds or the timer expires. While the
timer is active, Port 3 does not process any addi-
tional messages transmitting to Port 3.
Note: To change the intermessage time-out
amount, select the Intermessage Time-
Out field and enter the value in millisec-
onds.
After you have entered all of the configuration infor-
mation, select Save. The Information screen dis-
plays a confirmation message indicating that the
configuration is saved (see Figure 4.8). Select Ok to
close the Information screen. Select Revert to
return to the previously saved configuration.
Figure 4.8 SEAbus Device List Menu