8 DTU3005P Profibus Application Notes
Siemens Energy & Automation, Inc. 45
8 DTU3005P Profibus
Application Notes
8.1 System Overview and
Configuration
The DTU3005P is an intelligent transfer unit that
transfers data between SEAbus devices on Port 2
and a Profibus-DP host on Port 1. Port 3 is used as a
Passthrough port in which all messages received are
simply passed through to the SEAbus devices on
Port 2.
Port 3 on the DTU3005P is also used to send and
receive configuration information from a personal
computer running the DTU3005P Configuration soft-
ware. The communications parameters (baud rate,
data bits, parity, etc.) and timing parameters are con-
figured for the SEAbus ports using this software as
well as the DTU3005P address on the Profibus net-
work.
8.2 Profibus and SEAbus Device
Configuration
The list of SEAbus devices that data is transferred
from can be set up in two different ways:
1. Using the DTU3005P Configuration software
2. Using the user parameter area of the Profibus-
DP slave configuration sent by the Profibus host
If the SEAbus device configuration has been set up
using the Configuration software, it will be overrid-
den by a valid SEAbus device list received in the
Profibus user parameter data. The format of the
Parameter Data in the slave configuration is shown
in Ta b le 8 .1.
*For more information,see the device type codes
list in Section 8.4.
Any number of parameter bytes from 0 to 65 are
accepted by the DTU3005P. If the SEAbus devices
are configured through the Profibus-DP interface in
the user parameter data, only the number of bytes
required to configure the desired number of devices
is required. Additional bytes are ignored by the
DTU3005P, if present.
Note: When a valid SEAbus device list is
received in the user parameter area of the
Profibus-DP slave configuration, the new
device list is stored in non-volatile mem-
ory and used each time the DTU3005P is
powered up (unless overwritten by a new
Profibus-DP slave configuration message
or changed with the Configuration soft-
ware.)
8.3 Profibus Input/Output
Configuration
The input/output configurations are provided in the
Device Database file (PNTL3005.GSD) for the
DTU3005P unit (see Ta ble 8 .2 ):
8.4 Profibus Input Data
The input data transferred to the Profibus host will
vary depending on the configured input length and
the data read from a specific SEAbus device. When
16 words of input are configured, a special subset of
the collected real-time data for each type of device
is transferred.
For all other input configurations, the real-time data
as presented in Appendix C of the DTU3005P man-
ual is transferred. The data will be transferred
exactly as presented in the manual with three
exceptions:
Table 8.1 Slave Configuration Format
Byte Designation
0 Must be set to 0
1 Number of SEAbus devices being configured
2 Device Type Code for Device 0 (1st device)*
3 SEAbus Address for 1st device
4 Device Type Code for Device 1 (2nd Device)*
5 SEAbus Address for Device 1 (2nd Device)
.
.
.
Device Type Code and Address for Devices 2-30*
64 Device Type Code for Device 31 (if required)*
65 SEAbus address for Device 31 (if required)
Table 8.2 DTU3005P Input/Output Configurations
16 Words In, 0 Words Out 24 Words In, 0 Words Out
16 Words In, 4 Words Out 24 Words In, 4 Words Out
32 Words In, 0 Words Out 40 Words In, 0 Words Out
32 Words In, 4 Words Out 40 Words In, 4 Words Out
48 Words In, 0 Words Out 56 Words In, 0 Words Out
48 Words In, 4 Words Out 56 Words In, 4 Words Out
60 Words In, 0 Words Out
60 Words In, 4 Words Out