Siemens DTU3005-B Betreibershandbuch Seite 66

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 120
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 65
Appendix C: Device Data Format
62 Siemens Energy & Automation, Inc.
C.5 Device Type: Static Trip III
Real-Time Device Data Stored in PLC (Static Trip III)
Real-Time Data Register Location in
PLC Block
Range or Contents
Current Phase A 0 0...65000 A
Current Phase B 1 0...65000 A
Current Phase C 2 0...65000 A
Current Ground 3 0...65000 A
Voltage L-N Phase A 4 0...400 V
Voltage L-N Phase B 5 0...400 V
Voltage L-N Phase C 6 0...400 V
Voltage L-L Phase AB 7 0...660 V
Voltage L-L Phase BC 8 0...660 V
Voltage L-L Phase CA 9 0...660 V
Kilowatts 10 -32000...32000 kW
Kilowatt Demand 11 -32000...32000 kW
Kilowatt Hours (Total) 12–13 -9999999...9999999 kWH
Kilowatt Hours (Reverse) 14–15 -9999999...0 kWH
Kilovolt-Amperes Reactive 16 -32000...32000 kVAR
Power Factor 17 -100...100
Frequency 18 400...700, 0.1 Hz
Breaker Counter 19 0...65000 cycles
Comm Status
Note: When bit numbers are
specified, Bit 15 is the
highest order bit in the
PLC register.
20 Bit Contents
15 Breaker failed to open
14 Comm Trip Brkr active
13 Current unbal. pickup
12 Comm Phase Unbalance
11 Comm Close Brkr active
10 Digital Shadow Protect
9 Max Data Activity
8 Breaker Pos (1 = closed)
7 Reverse Power pickup
6 Over Frequency pickup
5 Under Frequency pickup
4 Overvoltage pickup
3 Undervoltage pickup
2 Voltage unbal. pickup
1 Remote Trip
0 Min Data Activity
Breaker Status 21 Bit Contents
15 ST UP Disabled Target
14 Long-time Overload
13 Short Circuit Target
12 Ground Fault Target
11 Voltage Unbal. Target
10 Zone Interlock Out
9 Current Unbal. Target
8 Long-time Pickup
7 Reverse Power Target
6 Over Frequency Target
5 Under Frequency Target
4 Overvoltage Target
3 Undervoltage Target
2 Instantaneous Bypass
1 ST Local Cmd to Trip
0 Static Trip Reset
Seitenansicht 65
1 2 ... 61 62 63 64 65 66 67 68 69 70 71 ... 119 120

Kommentare zu diesen Handbüchern

Keine Kommentare