Appendix C: Device Data Format
108 Siemens Energy & Automation, Inc.
C.21 Device Type: 7UT513
Real-Time Device Data Stored in PLC (7UT513)
Function Register Location in
PLC Block
Range or Contents
Operat. meas. current L1 side
1 (I1_L1)
0 %
Operat. meas. current L2 side
1 (I1_L2)
1 %
Operat. meas. current L1 side
3 (I1_L3)
2 %
Operat. meas. current L1 side
2 (I2_L1)
3 %
Operat. meas. current L2 side
2 (I2_L2)
4%
Operat. meas. current L3 side
2 (I2_L3)
5 %
Operat. meas. current L1 side
3 (I3_L1)
6 %
Operat. meas. current L2 side
3 (I3_L2)
7 %
Operat. meas. current L3 side
3 (I3_L3)
8 %
Operat. meas. current IA 9 %
Operat. meas. current IB 10 %
General Status Word 1:
1
11 Bit Contents
15 Parameter set C is active (Valid)
14 Parameter set C is active (Status)
13 Parameter set B is active (Valid)
12 Parameter set B is active (Status)
11 Parameter set A is active (Valid)
10 Parameter set A is active (Status)
9 Device operative/healthy (Valid)
8 Device operative/healthy (Status)
7 >User defined annunciation 4 (Valid)
6 >User defined annunciation 4 (Status)
5 >User defined annunciation 3 (Valid)
4 >User defined annunciation 3 (Status)
3 >User defined annunciation 2 (Valid)
2 >User defined annunciation 2 (Status)
1 >User defined annunciation 1 (Valid)
0 >User defined annunciation 1 (Status)
General Status Word 2:
1
12 Bit Contents
15 Thermal overload prot.2: Current Warn. (Valid)
14 Thermal overload prot.2: Current Warn. (Status)
13 Thermal overload protection 2 active (Valid)
12 Thermal overload protection 2 active (Status)
11 Thermal overload prot.1: Current Warn. (Valid)
10 Thermal overload prot.1: Current Warn. (Status)
9 Thermal overload protection 1 active (Valid)
8 Thermal overload protection 1 active (Status)
7 >Trip stage from Buchholz protection (Valid)
6 >Trip stage from Buchholz protection (Status)
5 Measured value supervision of currents (Valid)
4 Measured value supervision of currents (Status)
3 General internal failure of device (Valid)
2 General internal failure of device (Status)
1 Parameter set D is active (Valid)
0 Parameter set D is active (Status)