KINCO
107
Bit Address Word Address PLC address Notes
X 00.000-00.047
X 0000-0047
Y 01.000-01.031
Y 0100-0131
WX 000.00-000.03 WX 0000-0003
WY 001.00-Y001.01 WY 0010-0011
Note:
The range of X, Y, WX, WY is according to the I/O assign. Make sure the I/O address before using the
register.
Note:
1. Communication setting
  EH series, only port1 supports procedure 2.Switch DIP and change special Internal Input
(WR) value to select procedure.
 EH150 seriesonly EHCPU***A/448/516/548 support procedure 2.
 EH PLC connect with PC only by procedure 1.
2. CPU related actions
EH150
 DIP 5 must be set on.
 If DIP 5 is on, which procedure (1 or2) to use by judging the value of the WR F037.The
highest bit of WR F037 must be on, so that the other bits can be written in. The data keep on,
when turn on the power again.
o By entering 0x8000, turn on the power again and value of the address is 0x0000.After
settings, communication with procedure 1.
o By entering 0xC000, turn on the power again and value of the address is 0x4000.After
settings, communication with procedure 2.
  The transmission speed of port 1 will be set with DIP 3, 4 switches
o 3 on, 4 off is 19200 bps
  The transmission speed of port 2 will be set with DIP 6, PHL switches.
o 6 off, PHL on is 19200 bps
MicroEH
  The transmission speed will be set with DIP switches
o SW1 on is 19200 bps
  Which procedure(1 or2) to use by judging the value of the WR F01A.Different with EH150,
The highest bit of WR F01A is optional, The data will reset when turn on the power again. If the
value of R 7F6 is set on, the data of WR F01A will be stored in Flash memory.
o 0x0000 for procedure 1.
o 0x8000 for procedure 2.
Note: if procedure 2 is set and written in Flash memory, external device (only supports
procedure 1) or ladder editor will not connect with it.
Cable Diagram
Programming cable, as follow: