KINCO
178
Supported Device
OMRON E5EZ-R3
Device Bit Address Word Address Format Notes
0.0 — 0.A (C0 read only)
1.0 — 1.2D (C1)
Var iab le ------
2.0 — 2.5B (C3)
DDD.H
H
Main addr indicates variable
type 0(C0),1(C1),2(C3)
subaddress indicates
address of variable type
Action Command ------
0-8
H
State 0-31 ------ DD
Show the bit value of 0001
(state)in C0
Abnormal Input 0 ------ D
The 6th value of C0
0001(state) Abnormal Input
Action Command address and other informations
Addr command content Notes
00:OFF(disable)
0 Communication write
01:ON (enable)
Before writing data, "Communication
write" command is "01” ON (enable)",
otherwise it writes disable
00:Run
1 Run/Stop
01:Stop
00:Setting value 0
01:Setting value 1
02:Setting value 2
2 Multi-segment SP
03:Setting value 3
Must set the value of variable(addr:3.1A )to
1(ON) for writing correctly, otherwise it
can’t write-in.
00:stop
3 AT execute/stop
01:AT execute
00:save
4 write-in mode
01:RAM
5 RAM storage 00
6 Soft reset 00