KINCO
181
Editing Macro, please refer to the type table:
Register Type
N32 Double
FN Float
DTN Float
UTN Float
Input Float
SetPoint Float
Output Float
Gain Float
Tune I Float
Tune D Float
PID
Mode Double
IN BIT
QN BIT
PIN Float
PQN Float
NT Double
FT Float
B BIT(the attribute of B is the same as N32 in the PLC software)
BT BIT(the attribute of BT is the same as NT in the PLC software)
Note:
1、 The configuration in OPTO 22 software must be the same as the configuration in
EV5000 software:
true:e.g.: define Float in the OPTO 22 software,F1
Select FN device in the EV5000 software, address: 1.
Communicate correctly
error:e.g.: define Float in the OPTO 22 software,F0001
Select FN device in the EV5000 software, address: 1.
Communicate error
2、 PIDSN correspondence
If it set up PID1 in the OPTO 22 software, it can show the values of Input, SetPoint, Output,
Gain, Tune I, Tune D, and Mode.
In the Ev5000 software, PIDSN format DDDDD.DD, Address can be written in 1.**.( the main
address in front of decimal point corresponding to the OPTO 22 of PID1 1 ,sub-addr refer to
the table. the table as follows:
Sub Address(Example PID1,1 is sub address) Corresponding Value
1.00 Input
1.01 SetPoint
1.02 Output
1.03 Gain
1.04 Tune I
1.05 Tune D
Kommentare zu diesen Handbüchern