KINCO
66
range. In the setting mode
4707H
Lower-limit of temperature
range
The data content should not be lower than the temperature
range. In the setting mode
4708H PB Proportional band
1 to 9999, unit is 0.1. In the adjusting mode
4709H Ti Integral time
0~9999. In the adjusting mode
470AH Td Derivative time
0~9999. In the adjusting mode
470BH Heating/Cooling hysteresis 0~9999
4710H Input temperature sensor type
In the setting mode
4711H Control method
0: PID (default), 1: ON/OFF, 2: manual tuning. In the setting
mode
4712H Heating/Cooling control cycle
0 to 99 second, 0:0.5s, in the adjusting mode
or
, when it is under the control of PID
4713H
Proportional control offset error
value
0%~100%
4714H Temperature regulation value
-99.9~99.9. in the adjusting mode
4715H Alarm 1 type
Please refer to the contents of the “Alarm Outputs” for detail.
In the setting mode
4716H Alarm 2 type
Please refer to the contents of the “Alarm Outputs” for detail.
In the setting mode
4717H
Temperature unit display
selection
o
C : 1 (default),
o
F : 0. in the setting mode
4718H
Heating/Cooling control
Selection
Heating: 0 (default), Cooling: 1. in the setting mode
4719H Control Run/Stop setting
Run: 1 (default), Stop: 0. in the running mode
471AH
Communication write-in
selection
Communication write in disabled: 0 (default),
Communication write in enabled: 1.
In the setting mode
471BH Software Version V1.00 indicates 0 x 100