7 Troubleshooting
Siemens Energy & Automation, Inc. 43
7 Troubleshooting
Use this table to troubleshoot any errors that might occur when using the DTU3005P.
Problem Possible Cause(s) Action
Runtime error occurs
when starting the
program
The Editor program was started from an
icon on the desktop.
Close the DOS window and start the program
again.
From the DOS prompt, locate the DTU3005.BAT
file and execute it.
The CPU is greater than 300 MHz. Third-party program to slow down CPU clock
speed is required.
Project is not down-
loading to DTU unit
Wiring Verify wiring from PC to DTU.
Missing Null modem A Null modem is required between the PC and
DTU for communication.
DTU is not in Configuration Mode Power unit down, enable Dip Switch 3, and then
power unit on. Flashing green light indicates that
the DTU is in Configuration mode.
Running software on Windows NT system Use software only on systems running Windows
95 or 98.
DTU is not communi-
cating with Profibus
Master
Incorrect settings
- Address
- Baud Rate
Verify address and baud rate settings.
Wiring Verify wiring from DTU to Profibus-DP Master.
DTU is in Configuration mode Power down unit, turn all Dip Switches off, and
then power the unit back on. Steady green light
indicates that the DTU is in normal operation
mode.