OPTIONS
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2002/2003
6/17 Version D
6.6 Recommended protection
We recommend slow-acting line fuses to protect the feeder cable. The rule of thumb "input current (max. continuous current) of
the drive inverter + ~30%" can be used to determine the rated fuse current for fuses, circuit-breakers, motor protection circuit-
breakers, bimetallic protective elements. When using motor protection circuit-breakers it must be ensured that the devices used
are certified for drive inverter operation. We recommend 3RU.... or 3RV.... devices or 3NA... fuses.
MICROMASTER, MICROMASTER Vector
Line supply voltage
Version
MM = MICROMASTER
MMV = MICROMASTER Vector
Recommen-
ded rated fuse
currents
A
Recommended
fuse
utilization category
gG/gL
Order No.
Recommended circuit-
breaker
Order No. (b)
1-ph. 230 V AC MM12, MMV12, MM25, MMV25, MM37, MMV37 10 3NA3803 5SX2 110 -6
MM55, MMV55, MM75, MMV75 16 3NA3805 5SX2 116 -6
MM110, MMV110, MM150, MMV150, 20 3NA3807 5SX2 120 -6
MM220, MMV220 20 3NA3810 5SX2 125 -6
MM300, MMV300 (a) 32 3NA3812 5SX2 132 -6
1-ph. 230 V AC,
3-ph. 230 V AC
MM12/2, MMV12/2, MM25/2, MMV25/2, MM37/2,
MMV37/2, MM55/2, MMV55/2, MM75/2, MMV75/2
10 3NA3803 5SX2 310 -6
MM110/2, MMV110/2, MM150/2, MMV150/2 16 3NA3805 5SX2 316 -6
MM220/2, MMV220/2 20 3NA3807 5SX2 320 -6
MM300/2, MMV300/2 (a) 25 3NA3810 5SX2 325 -6
Only 3-ph. 230V AC MM400/2, MMV400/2 32 3NA3812 5SX2 332 -6
3-ph. 380 V - 500 V
AC
(c)
MM37/3, MMV37/3, MM55/3, MMV55/3, MM75/3,
MMV75/3, MM110/3, MMV110/3, MM150/3, MMV150/3,
10 3NA3803 5SX2 310 -6
MM220/3, MMV220/3, MM300/3, MMV300/3 16 3NA3805 5SX2 316 -6
MM400/3, MMV400/3, MM550/3, MMV550/3 20 3NA3807 5SX2 320 -6
MM750/3, MMV750/3 25 3NA3810 5SX2 325 -6
Information on the tables: "Recommended fusing for MICROMASTER & MIDIMASTER"
3NA... fuses are not UL certified,
5SX... circuit-breakers with characteristic type B from 6A to 50A & characteristic type C from 0.5A to 50A, are
certified for UL 1077 and CSA 22.2 No. 235 - M 89 and can be used as "supplementary protectors"
- not available
- additional data on 3NA... und 5SX2... fuses are provided in the Catalog for Installation Technology I 2.1 or in the NS
K Catalog
(a) MM(V)300 and MM(V)300/2 require an external reactor for 1-phase voltages (e.g. 4EM4807-8CB) and a 32A line
fuse.
(b) Characteristic type A (fast acting) = 5SX2 ... -5 > cable protection for control systems, limited semiconductor
protection
Characteristic type B (slow-acting) = 5SX2 ... -6 > cable protection for socket outlets
Characteristic type C (slow-acting) = 5SX2 ... -7 > general cable protection, suitable for motors
(c) Rated voltage for circuit-breakers = 230/400V (max. 440V +10%)
Kommentare zu diesen Handbüchern