ENGINEERING INFORMATION AND INSTRUCTIONS
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2002/2003
3/17 Version D
Maximum output current referred to the pulse frequency
As a result of higher switching losses at increased switching frequencies, the maximum continuous current (100 %) of some drive inverters
can be reduced, if a pulse frequency other than the standard pulse frequency is selected.
Type Perm. load as a % of the
max. continuous current
at 16 kHz at 8 kHz
MMV75/3 80 100
MMV110/3 50 80
MMV150/3 50 80
MMV220/3 80 100
MMV300/3 50 80
MMV400/3 50 80
MMV550/3 50 80
MMV750/3 50 80
Note: If the pulse frequency is either 2 or 4 kHz, the above mentioned drive inverters are not de-rated.
Type
Perm. load as a % of the
max. continuous current
at 16 kHz at 8 kHz
MDV550/2 39 75
MDV750/2 64 90
MDV1100/2 55 75
MDV1500/2 38 68
MDV1850/2 43 79
MDV2200/2 38 68
MDV750/3 55 100
MDV1100/3 39 75
MDV1500/3 64 90
MDV1850/3 55 75
MDV2200/3 40 75
MDV3000/3 47 88
MDV3700/3 40 75
MDV550/4 75 100
MDV750/4 55 100
MDV1100/4 39 75
MDV1500/4 64 90
MDV1850/4 55 75
Note: For all other Size 6 drive inverters, 575 V and Size 7 MIDIMASTER Vector, the pulse frequency can either be 2 or 4 kHz.