Communications / interfaces
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2001/2002
4/2 Version C4
4. COMMUNICATIONS &
INTERFACES
4.1 Communications, operator control
and display elements
MICROMASTER, MICROMASTER Vector and
MIDIMASTER Vector have the identical operator control and
display elements.
The AC drive inverters can either be controlled, data read-out
and parameterized at the unit itself or also externally:
1. At the drive inverter, using:
· Membrane keypad with 7 keys - this is provided as
standard
· Optional OPM2 operator panel with plain text display
· Or control terminal strip
2. Externally, using:
· Serial RS 485 interface
· Optional OPM2 operator panel with plain text display
· Optional PROFIBUS module
· Or a PC with DRIVE-MONITOR
4.2 Standard operator panel
The standard operator panel has 7 keys as well as an LED
display comprising 4 x 7 segments, and has the following
functions:
· Starting the drive inverter
· Operator control functions:
· Motor ON/OFF, increasing/decreasing the motor
frequency setpoint;
· "Clockwise/counter-clockwise rotation" selection and the
jog frequency using the JOG key
· Starting and stopping with a pre-set frequency
· Displaying motor frequency setpoints and actual values
· Displaying and changing parameters
· Displaying the AC drive inverter status
· Displaying alarm messages
· Displaying and resetting fault messages
The function keys can be individually inhibited. The OFF key
is always active for safety reasons.
LED
display
Key, CLOCKWISE/
COUNTER-CLOCKWISE
direction of rotation
RS485
interface
ON
key
OFF
key
Removable
cover
JOG
key
INCREASE
frequency
DECREASE
frequency
Parameterizing
key
P
Jog
Fig. 1: Standard operator panel
There is a 9-pin SUB-D connector
(X502) on the membrane keypad which forms the RS485
interface. The optional PROFIBUS module or the plain text
operator panel can be connected to this interface. The drive
can be connected directly to a PC via the RS232 interface on
the plain text operator panel.
4.3 Serial RS485 interface
The RS485 interface of the MICROMASTER and the
MIDIMASTER operates with the USS protocol, can be
networked with 31 nodes (stations) via a bus and allows a
max. data transfer rate of 19.2 kbit/s.
It is possible to access the RS485 interface via a SUB-D
connector (refer to Table 1 for the pin assignment) - for
6SE32 drives – via the control terminal strip.
1
2
3
45
6
7
8
9
Fig. 2: Pin assignment of the SUB-D connector