COMMUNICATIONS / INTERFACES
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2001/2002
4/11 Version C3
4.12 Parameter list
Legend:
• = These parameters can also be changed while the drive inverter is operational.
²²² = The setting value depends on the drive inverter type.
Parameter Function Range [factory setting]
MICROMASTER MICRO/MIDIMASTER Vector
P000 Operating display - -
P001 • Display mode 0 - 8 [0] 0 - 9 [0]
P002 • Ramp-up time (seconds) 0 – 650.0 [10.0] 0 – 650.0 [10.0]
P003 •
Ramp-down time (seconds) 0 – 650.0 [10.0] 0 – 650.0 [10.0]
P004 • Smoothing time (seconds) 0 – 40.0 [0.0] 0 – 40.0 [0.0]
P005 • Digital frequency setpoint (Hz) 0.00 – 400.00 [5.00] 0.00 – 650.00 [5.00]
P006 Frequency setpoint source selection 0 - 2 [0] 0 - 3 [0]
P007 Keypad control 0 - 1 [1] 0 - 1 [1]
P009 • Parameter protection setting 0 - 3 [0] 0 - 3 [0]
P010 Display scaling - 0.00 – 500.00 [1.00]
P011 Frequency setpoint memory 0 - 1 [0] 0 - 1 [0]
P012 • Minimum motor frequency (Hz) 0.00 - 400.00 [0.00] 0.00 - 650.00 [0.00]
P013 • Maximum motor frequency (Hz) 0.00 - 400.00 [50.00] 0.00 - 650.00 [50.00]
P014 • Skip frequency 1 (Hz) 0.00 - 400.00 [0.00] 0.00 - 650.00 [0.00]
P015 • Automatic restart after line failure 0 - 1 [0] 0 - 1 [0]
P016 • Start on the fly 0 - 2 [0] 0 - 4 [0]
P017 • Smoothing type 1 - 2 [1] 1 - 2 [1]
P018 • Automatic restart after fault 0 - 1 [0] 0 - 1 [0]
P019 • Skip frequency bandwidth 0.00 - 10.00 [2.00] 0.00 - 10.00 [2.00]
P020 • Ramp time for start on the fly (s) 0.5 - 25.0 [2.00] -
P021 • Minimum analog frequency (Hz) 0.00 - 400.00 [0.00] 0.00 - 650.00 [50.00]
P022 • Maximum analog frequency (Hz) 0.00 - 400.00 [50.00] 0.00 - 650.00 [50.00]
P023 • Analog input 1 type 0 - 2 [0] 0 - 3 [0]
P024 • Analog setpoint addition 0 - 2 [0] 0 - 2 [0]
P025 • Analog output 1 - 0 - 105 [0]
P026 • Analog output 2 - 0 - 105 [0] MIDI
P027 •
Skip frequency 2 (Hz)
0.00 - 400.00 [0.00] 0.00 - 650.00 [0.00]
P028 • Skip frequency 3 (Hz) 0.00 - 400.00 [0.00] 0.00 - 650.00 [0.00]
P029 • Skip frequency 4 (Hz) 0.00 - 400.00 [0.00] 0.00 - 650.00 [0.00]
P031 • Jog frequency right (Hz) 0.00 - 400.00 [5.00] 0.00 - 650.00 [5.00]
P032 • Jog frequency left (Hz) 0.00 - 400.00 [5.00] 0.00 - 650.00 [5.00]
P033 • Jog ramp-up time (seconds) 0 - 650.0 [10.0] 0 - 650.0 [10.0]
P034 • Jog ramp-down time (seconds) 0 - 650.0 [10.0] 0 - 650.0 [10.0]
P040 Positioning function - 0.1 [0]
P041 • Fixed frequency 1 (Hz) 0.00 - 400.00 [5.00] 0.00 - 650.00 [5.00]
P042 • Fixed frequency 2 (Hz) 0.00 - 400.00 [10.00] 0.00 - 650.00 [10.00]
P043 • Fixed frequency 3 (Hz) 0.00 - 400.00 [15.00] 0.00 - 650.00 [15.00]
P044 • Fixed frequency 4 (Hz) 0.00 - 400.00 [20.00] 0.00 - 650.00 [20.00]