ENGINEERING INFORMATION AND INSTRUCTIONS
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2002/2003
Version D 3/6
3.3 Degrees of protection
The IP number defines the
degree of protection against the
ingress of dirt, foreign bodies,
water etc. (Ingress Protection;
IP) for the associated drive
inverter.
MICROMASTER and
MICROMASTER Vector have
degree of protection IP20 (this
corresponds to the US NEMA 1
Class).
MIDIMASTER Vector models
with degree of protection IP21
(this corresponds to the US
NEMA 1 Class) or IP56 (this
corresponds to the US NEMA
4/12 Class).
The significance of the
individual IP class numbers
referred to the protection
against the ingress of dirt etc. is
explained in Table 4:
First number
IPXxx
0 No specific protection
1 Protected against solid
objects with a diameter of 50
mm
2 Protected against solid
objects with a diameter larger
or equal to 12 mm
3 Protected against solid
objects with a diameter larger
or equal to 2.5 mm
4 Protected against solid
objects with a diameter larger
or equal to 1 mm
5 Protected against dust
(limited ingress)
6 Protected against dust
(totally)
Second number
IpxXx
0 No specific protection
1 Protected against water falling
vertically
2 Protected against vertically
falling spray water if the equipment
is tipped up to 15 degrees to the
vertical
3 Protected against vertically
falling spray water if the equipment
is tipped up to 60 degrees to the
vertical
4 Protected against water sprayed
from all directions
5 Protected against low-pressure
water jets from all directions
6 Protected against low-pressure
water jets from all directions
7 Protected against immersion
between 15 cm and 1 m
8 Protected against immersion
under pressure
Third number
(not specified)
IPxxX
0 No specific
protection
1 Protected
against impact up
to 0.225 J
2 Protected
against impact up
to 0.375 J
3 Protected
against impact up
to 0.5 J
5 Protected
against impact up
to 2.0 J
7 Protected
against impact up
to 6.0 J
9 Protected
against impact up
to 20.0 J
Rear cabinet panel
Fig. 2: MIDIMASTER Vector with degree of protection IP56 – installed in a housing
MIDIMASTER Vector, with degree of protection IP56/NEMA 4/12, can be accommodated in a larger housing, whereby the heatsink
protrudes through the rear cover of the unit. This ensures that the heat from the drive inverter is dissipated to the ambient air
without the need for additional cooling fans. This guarantees the IP56 degree of protection. Only the minimum mounting clearance
of 150mm to the next drive unit must be observed.