Siemens NAN 67 Series Wartungshandbuch Seite 148

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 318
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 147
11-4
Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
11.3 Subtract Integer
A signal state of 1 at the Enable (EN) input activates the Subtract Integer
instruction. This instruction subtracts input IN2 from IN1. The result can be
scanned at OUT. If the result is outside the permissible range for an integer,
the OV and the OS bit of the status word are 1 and the ENO is 0.
Certain restrictions apply to the placement of integer math boxes (see
Section 6.1).
Table 11-3 Subtract Integer Box and Parameters
LAD Box
Parameter Data Type Memory Area Description
SUB I
EN BOOL I, Q, M, D, L Enable input
SUB_I
EN ENO
ENO BOOL I, Q, M, D, L Enable output
IN1
EN ENO
IN1 INT I, Q, M, D, L First value (from which to subtract)
IN1
IN2 OUT
IN2 INT I, Q, M, D, L Value to subtract from first value
IN2 OUT
OUT INT I, Q, M, D, L Result of subtraction
Status Word Bits
BR CC 1 CC 0 OV OS OR STA RLO FC
Write x x x x x x 1 x x
I 0.0
A signal state of 1 at input I 0.0 activates the
SUB_I box. The result of the subtraction
MW0 – MW2 is put into memory word MW10.
If the result is outside the permissible range
for an integer or the signal state of input I 0.0
is 0, output Q 4.0 is set.
Q 4.0
SUB_I
IN2
EN ENO
MW2 MW10
IN1MW0
S
Function is executed (EN = 1):
NOT
OUT
Figure 11-3 Subtract Integer
Description
Integer Math Instructions
Seitenansicht 147
1 2 ... 143 144 145 146 147 148 149 150 151 152 153 ... 317 318

Kommentare zu diesen Handbüchern

Keine Kommentare