Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
18.4 Jump in the Block If RLO = 0 (Jump-If-Not)
The Jump-If-Not instruction corresponds to a “go to label” instruction that is
executed if the RLO is 0.
You can use this instruction in all logic blocks: organization blocks (OBs),
function blocks (FBs), and functions (FCs).
Table 18-3 Jump-If-Not Element and Parameters
LAD Element Parameter Data Type Memory Area Description
JMP N
<address>
Name of a
label
The address determines the mark to
which the jump is made when the
RLO = 0.
Status Word Bits
BR CC 1 CC 0 OV OS OR STA RLO FC
Write 0 1 1 0
CAS1
JMPN
R
I 0.4 Q 4.1
Network 1
Network 3
If the signal state of input I 0.0 is 0, the
jump to label CAS1 is executed. The
instruction to reset output Q 4.0 is not
executed, even if the signal state of input
I 0.3 is 1.
None of the instructions between the
jump operation and the label is executed.
I 0.0
R
I 0.3 Q 4.0
CAS1
Network 2
Figure 18-4 Jump-If-Not
Description
Jum
p
Instructions