18-3
Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
18.2 Jump in the Block If RLO = 1 (Unconditional Jump)
The Unconditional Jump instruction corresponds to a “go to label”
instruction. No additional LAD element may be positioned between the left
power rail and the operation. None of the instructions between the jump
operation and the label is executed.
You can use this instruction in all logic blocks: organization blocks (OBs),
function blocks (FBs), and functions (FCs).
Table 18-1 Unconditional Jump Element and Parameters
LAD Element Parameter Data Type Memory Area Description
JMP
<address>
Name of a
label
The address determines the mark to
which the absolute jump is made.
Status Word Bits
BR CC 1 CC 0 OV OS OR STA RLO FC
Write
CAS1
CAS1
JMP
R
I 0.4
Q 4.1
Network 1
Network X
The jump is executed every time. None of
the instructions between the jump
operation and the label is executed.
Figure 18-2 Unconditional Jump: Go to Label
Description
Jum
p
Instructions