Ladder Logic (LAD) for S7-300 and S7-400
C79000-G7076-C504-02
18.3 Jump in the Block If RLO = 1 (Conditional Jump)
The Conditional Jump instruction corresponds to a “go to label” instruction if
RLO = 1. Use the Ladder element “Jump unconditional” for this operation
but only with an advance logic operation. The conditional jump is only
executed when the result of this logic operation is RLO = 1. None of the
instructions between the jump operation and the label is executed.
You can use this instruction in all logic blocks: organization blocks (OBs),
function blocks (FBs), and functions (FCs).
Table 18-2 Conditional Jump Element and Parameters
LAD Element Parameter Data Type Memory Area Description
JMP
<address>
Name of a
label
The address determines the mark to
which the jump is made when the
RLO = 1.
JMP
Network 1
Status Word Bits
BR CC 1 CC 0 OV OS OR STA RLO FC
Write 0 1 1 0
I 0.0
Q 4.0
I 0.3
If the signal state of input I 0.0 is 1, the
jump to label CAS1 is executed. The
instruction to reset output Q 4.0 is not
executed, even if the signal state of input
I 0.3 is 1.
CAS1
Q 4.1
I 0.4
Network 3
R
R
CAS1
Network 2
Figure 18-3 Conditional Jump: Go to Label