Commissioning and Diagnostics
7-18
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
7.6.2 Master PROFIBUS address
Definition
The DP address of the DP master is stored in the master PROFIBUS address
diagnostic byte:
The master that parameterized the DP slave
The master that has read and write access to the DP slave
Master PROFIBUS address
Table 7-11 Structure of the master PROFIBUS address (byte 3)
Bit Description
0 to 7 DP address of the DP master that parameterized the DP slave and
has read/write access to that DP slave.
FF
H
: DP slave has not been parameterized by a DP master.
7.6.3 Manufacturer ID
Definition
The manufacturer identification contains a code specifying the DP slaves type.
Manufacturer ID
Table 7-12 Structure of the manufacturer identification (bytes 4 and 5)
Byte 4 Byte 5 Manufacturer identification for
80
H
E2
H
IM 151-7 CPU