Getting Started
2-19
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
2.10 10th step: Commissioning and test run of the
IM 151-7 CPU and S7-300
Se-
quence
Action Result
1 In the SIMATIC Manager, navigate to the block
container of the S7-300 and insert an empty
organization block with the name OB 86 into the
block container.
This block ensures that the S7-300-CPU does not
switch to STOP if a station of the IM 151-7 CPU
fails/recovers.
Generate OB 82 in the same way.
2 Make sure that the mode selector of the S7 and IM
is set to STOP
Switch on the PS of the S7-300 and the PS of the
ET 200S.
The IM 151-7 CPU and S7-300-CPU
request a memory reset.
3 Reset the memory of the IM 151-7 CPU and
S7-300-CPU as follows:
Press/rotate the mode selector to MRES. Hold
the mode selector at this position until the
STOP LED lights up for the second time and
then remains lit (approx. 3 seconds). Then
release the mode selector.
You must press/rotate the mode selector back
to MRES within 3 seconds. The STOP LED
begins to flash rapidly and the CPU performs a
memory reset. You can now release the mode
selector. The CPU has completed the memory
reset when the STOP LED remains
permanently lit again.
Both CPUs have undergone a memory
reset.
4 In the PLC menu of the SIMATIC Manager, select
the Load command to transfer the program and the
hardware configuration to the S7-300-CPU.
Confirm all windows that appear with Yes.
The program and configuration are
downloaded from the PD to the CPU.