Getting Started
2-6
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
2.3 3rd step: Commissioning the IM 151-7 CPU (ET 200S)
Note
On initial commissioning (condition when supplied) of the ET 200S, the CPU
can be accessed using the MPI address 2, HSA 31 and 187.5 kBaud.
Se-
quence
Description
1 Switch on the PS of the IM 151-7 CPU.
Result:
The 24 VDC LED lights up on the PS.
The PWR and SF LEDs light up on the PM.
All LEDs light up on the IM 151-7 CPU, the SF, BF, FRCE and RUN LEDs go out again and
the STOP LED starts to flash rapidly. The IM 151-7 CPU performs a memory reset.
2 Then press the two buttons which are connected to the DI module. The 1 LED lights up when
the buttons at terminal 1 and 3 are pressed.
The 5 LED lights up when the buttons at terminal 5 and 7 are pressed.
3 Switch on your PD and start the SIMATIC Manager on the Windows Desktop.
4a In the main menu of the SIMATIC Manager, click on Tools and select the menu item Set
PD/PC Interface. Configure the PD/PC interface as follows:
4b
Note: The communication processor may have a different name on your PD. It is important to
make sure that the MPI version is set.
5 Confirm the settings with OK and close the ”Set PD/PC Interface” program.