DP Master Module
6-4
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
Behavior of the IM 151-7 CPU upon commissioning
The DP master module is mounted and the IM 151-7 CPU has been configured
as a DP master
IM 151-7 CPU goes into RUN mode with master functionality
The DP master module is mounted and the IM 151-7 CPU has not been
configured as a DP master
IM 151-7 CPU goes into RUN mode without master functionality
The DP master module is not mounted but IM 151-7 CPU has been configured
as a DP master
The behavior of the IM 151-7 CPU depends on the setting of the parameter
Start-up when preset configuration actual configuration:
Start-up when the preset configuration actual configuration = yes
IM 151-7 CPU goes into RUN mode
(see also Start-up of the IM 151-7 CPU as a DP master)
Start-up when preset configuration actual configuration = no
IM 151-7 CPU remains in STOP mode
(see also Start-up of the IM 151-7 CPU as a DP master)
Initializing the DP master system
In addition, the initialization time monitor for the DP slave can be set with the
Monitoring time for transfer of parameters to modules parameter.
This means that the DP slaves must be initialized and parameterized by the
IM 151-7 CPU (as DP master) within the set time period.