Addressing
3-2
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
3.1 Slot-Oriented Addressing of the I/O Modules
Slot-Oriented Address Allocation
In slot-oriented addressing (default addressing) each slot number in a module is
allocated an address area in the IM 151-7 CPU.
Depending on the type of I/O module, the addresses are digital or analog (see
Table 3-1). The address allocation is not fixed and can be changed, but there is a
default address area.
0
127
256
1263 2047
1 byte per digital module,
Motor starter or
4 IQ SENSE
16 bytes per analog module
or technology
module
Direct communication
Figure 3-1 Structure of the default address area
Slot Assignment
The figure below shows an ET 200S configuration with digital electronic modules,
analog electronic modules, process-related modules and the slot assignment.
Interface module
PM-E power module
2DI 24 V DC
2DI 24 V DC
2AO U
2AI RTD
1Count 24V/100kHz
1SSI
Termin. elem.
SSI
456 10879
Slot
DP master module
Figure 3-2 Slots on the ET 200S