Cycle and Response Times
9-4
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
User program scanning time:
The user program scanning time is made up of the sum of the execution times for the
instructions and SFCs called. These execution times can be found in the instruction
list. You also have to multiply the user program scanning time by an interface
module-specific factor.
In the IM 151-7 CPU, this factor depends on the following:
Table 9-3 Dependency of the user program scanning time
Dependency
Range
The number of modules inserted 0 to 63
You can calculate the factor for your application approximately using the following
rule of thumb for the IM 151-7 CPU:
1.1
+ 0.005 x number of modules
= Multiplier for your user program
Delay of the inputs and outputs
You have to take into account the following delay times, depending on the
expansion module:
For digital inputs: The input delay time
For digital outputs: Negligible delay times
For analog inputs: Cycle time of the analog input
For analog outputs: Response time of the analog output
Extending the cycle by nesting interrupts
Table 9-4 shows typical extensions of the cycle time through nesting of an
interrupt. The program runtime at the interrupt level must be added to these. If
several interrupts are nested, the corresponding times need to be added.
Table 9-4 Extending the cycle by nesting interrupts
Interrupts
IM 151-7 CPU
Process interrupt 500 µs
Diagnostic interrupt 600 µs
Time-of-day interrupt 400 µs
Delay interrupt 300 µs
Watchdog interrupt 150 µs
Status interrupt/update interrupt/manufacturer-specific
interrupt
600 µs
Programming/access error/runtime system error 400 µs