Seitenansicht 104
Commissioning and Diagnostics
7-23
ET 200S IM 151-7 CPU Interface Module
A5E00058783-04
Structure of the interrupt data with process interrupt (from Byte y+4 onwards)
With the process interrupt (in byte y+1, code 02
H
stands for a process interrupt),
the 4 byte interrupt information which you transfer in the intelligent slave with the
SFC 7 ”DP_PRAL” and SFB 75 ”SALRM” when the process interrupt is generated
for the master, is transferred from byte y+4 onwards.
Structure of the interrupt data when a diagnostic interrupt is generated by a
mode change at the intelligent slave (from Byte y+4 onwards)
In the byte y+1, the code stands for diagnostic interrupt (01
H
). The diagnostic data
contains the 16 byte status information for the CPU. The following figure shows the
assignment of the first 4 bytes of the diagnostic data. The next 12 bytes are always
0.
The content of these bytes corresponds to the content of data record 0 for
diagnosis in STEP 7 (in this case not all bits are assigned).
Byte y+4
Byte y+5
Byte y+6
0: Operating mode RUN
1: Operating mode STOP
0: IM 151-7 CPU ok
1: IM 151-7 CPU faulty
0
1
000 0
1
0
0
00000
1
Identifier for the address area of the
intermediate memory (constant)
0000000
Byte y+7
00000000
70654 13 2 Bit no.
70654 13 2 Bit no.
7065 4 13 2 Bit no.
7065 4 13 2 Bit no.
Figure 7-7 Byte y+4 to y+7 for the diagnostic interrupt (changed operating status of the