UM344-2 CALIBRATION AND MAINTENANCE
September 1995
6
-
1
6.0 CALIBRATION AND MAINTENANCE
This section describes calibration, preventive maintenance, and troubleshooting
The Maintenance section has preventive maintenance procedures that are employed to prevent conditions
from occurring that would be detrimental to the reliability of the transmitter. Should a malfunction occur,
troubleshooting procedures will assist in minimizing down-time. This section also includes transmitter
removal and replacement procedures, recommended spare and replacement parts, and an exploded view
drawing with a parts list.
WARNING
In Division 1 areas, where an explosion-proof rating is required, remove
power from the transmitter before removing the transmitter's end cap
for access to the electrical terminal compartment.
The MXC is approved for use in non-hazardous areas only.
6.1 CALIBRATION
A transmitter is calibrated at the factory and should not require field calibration. Sections 6.1.2 and 6.1.3
describe field and bench calibration of a transmitter.
Transmitter calibration should be checked at least annually and the procedures in this section performed if
out of tolerance.
An MXC is needed for calibration. It provides four calibration programs:
Ÿ DAC OUTPUT - Calibrates the Digital-to-Analog Converter that sets the transmitter's analog output
signal.
Ÿ WIDE mV - Calibrates the millivoltmeter for TC/mV inputs between -18.00 mV and 103 mV.
Ÿ NARROW mV - Calibrates the millivoltmeter for TC/mV inputs between -11.00 mV and 26.00 mV
Ÿ CURRENT SOURCE - Calibrates the transmitter’s current source that supplies a forcing current to
RTD/Ohm sensors.