UM344-2 MODEL DESIGNATION AND SPECIFICATIONS
September 1995
ESD Susceptibility ........................................................IEC severity level 4, 15 kV
8.3.6 Hazardous Area Classification
Before installing, applying power to, or servicing a transmitter, see the transmitter's nameplate and the
Table in section 8.1 for the electrical classification. Contact Moore Products Co. for latest approvals and
certifications.
The transmitter has been designed to meet the following:
FM/CSA - (CSA approval has been granted. FM approval was pending at the time this User’s Manual was
prepared.)
Intrinsically Safe: Class I, Division 1, Groups A, B, C, and D
Class II, Division 1, Groups E, F and G
Class III, Division 1
Explosion Proof: Class I, Division 1, Groups B, C and D
Class II, Division 1, Groups E, F, and G
Class III, Division 1
Non-Incendive: Class I, Division 2, Groups A, B, C and D
Class II, Division 2, Groups E, F, and G
Class III, Division 2
Electronics Housing: NEMA 4X, IP 66/IP 68
CENELEC
Flame Proof: EEx d IIC T4 Tamb 85°C
T6 Tamb 60°C
T8 Tamb 50°C
BASEEFA
Ex N IIC T4 (Tamb = -40°C to 85°C)
Ex N IIC T5 (Tamb = -40°C to 60°C)
Ex N Use - Install a voltage limiting device that will prevent loop terminal voltage
from exceeding 42 Vdc.
Electronics Housing: IP66/IP68
EMC Compatibility: A Declaration of Conformity showing accordance with EN45014 is located on the
following page.
SAA Certification The transmitter has been assessed to the entity concept. Consider the following
electrical parameters during installation.
Maximum Input Voltage (Ui) 42V
Maximum Input Current (Ii) 180 mA
Maximum Internal Capacitance (Ci) 0 µF
Maximum Internal Inductance (Li) 0 mH