ON-LINE AND OFF-LINE OPERATION UM344-2
September 1995
2. From the above Warning screen, press one of the following
two keys:
DOWNLOAD - start a download. The MXC will show the
Download Wait screen and then the Download Complete
screen. The new configuration is now stored in the
transmitter.
ABORT - return to the previous screen.
5.1.3 Local Transmitter
Operation
The Model 344 has two local pushbuttons labeled FS (Fullscale)
and Z (Zero) located on the housing. These are used to set
range and damping when the controller block is configured
“OFF”. This is detailed in the following sections.
When the controller block is configured “ON” the ranging/
damping capabilities are not available. In this mode the
pushbuttons may be used to transfer between AUTO and
MANUAL control, change VALVE output, and change the
SETPOINT. This is detailed in the following sections.
Local Pushbutton Operation:
The “Pushbutton Mode” must be activated as described below to
use the Zero and Full Scale pushbuttons.
• The Pushbutton Mode is activated whenever either
pushbutton is pressed and held for a minimum of 5 seconds
and then released. The “PB” annunciator on the Digital
Meter will be lit while the Pushbutton Mode is active.
• The Pushbutton mode will automatically time-out after 1
minute.
• Failure to hold a pushbutton ON for a minimum of 5 seconds
will prevent entry into the Pushbutton mode.
• The pushbuttons are disabled when the transmitter is placed
in “CONFIGURATION HOLD,” as when downloading a
configuration.
Pushbuttons are enabled or disabled by jumper W1 on the
Electronics Module and are enabled by the factory. Jumpering
pins 2 and 3 equals ENABLE. When the jumper is in the
DISABLE position, the pushbuttons perform no function.
DOWNLOADING
CONFIGURATION
- PLEASE WAIT -
DOWNLOAD
COMPLETE
Kommentare zu diesen Handbüchern