CALIBRATION AND MAINTENANCE UM344-2
September 1995
6
-
12
If accuracy is within specifications, calibration is not required. Disconnect test equipment, re-connect
all wires and install enclosure cap.
6.1.4.2 Narrow/Wide Millivolt Calibration
Calibration equipment connections are as shown in Figure 6-4.
A. NARROW MILLIVOLT CALIBRATION
1. From the MXC, execute the FIND XMTR program then select CAL/TEST (F2) from the display
menu.
2. Step through the MXC screens using the PREV and NEXT buttons to select NARROW
MILLIVOLT calibration. Press SELECT (F4).
The MXC will display:
3. Adjust the output of the millivolt source to 26.000 mV.
4. Press CONT (F4). Screen will display:
5. Adjust the output of the millivolt source to -11.000 mV.
6. Press CONT (F4). Screen will return to SELECT
CALIBRATION menu shown here.
7. Press CONT (F4) to calibrate.
Press ABRT (F3) to quit without changing calibration.
8. Narrow Millivolt calibration is completed.
If no other calibrations are required, disconnect test equipment, reconnect all wires, and install
enclosure cap.
If Wide Calibration is required, retain test set-up and proceed to paragraph B.
B. WIDE MILLIVOLT CALIBRATION
1. From the MXC, execute the FIND XMTR program then select CAL/TEST (F2) from the display
menu.
2. Step through the MXC screens to select WIDE MILLIVOLT calibration.. Press SELECT (F4).
APPLY 26.000 mV TO
mV+ (1) AND mV- (3)
WITH COPPER WIRE
CONT
APPLY -11.000 mV TO
mV+ (1) AND mV- (3)
WITH COPPER WIRE
CONT
WARNING: BURNING
EPROM WILL CHANGE
CALIBRATION CHARAC-
TERISTICS
CONT
ABRT