UM344-2 INITIAL TRANSMITTER SET-UP
September 1995
3
-
1
3.0 INITIAL TRANSMITTER SET-UP
Before operating a Model 344 on-line, the instrument should be commissioned using the MXC and set-up
either at the bench or in the field. Commissioning consists of checking that the transmitter and the loop
are operational and that all configuration information is correct. This section contains step-by-step
procedures describing commissioning of the transmitter. For an in-depth discussion of transmitter
configuration, refer to Section 5.1 On-Line Operation.
3.1 COMMISSIONING TRANSMITTER ON THE BENCH OR IN THE FIELD
A Model 344 can be commissioned either before or after installation into the loop. Commissioning on the
bench before installation is suggested. A complete transmitter functional test can be performed and
configuration procedures can be practiced. If commissioning after installation, install the transmitter as
described in Section 4 and then return to this section. Configuration data for the transmitter will be
needed.
To commission the transmitter on the bench, make the connections shown in Figure 3-1. To commission
the transmitter in the field, make the connections shown in Figure 3-2 or those shown in Section 4.3.3,
Figure 4-1, 4-2, or 4-3. Connect the MXC in the loop either across the current sense resistor or, often
more conveniently, across the two signal terminals of the Model 344 (non-hazardous area only).
3.1.1 Test Equipment Needed
TEST EQUIPMENT DESCRIPTION (see Specifications, Section 8.3.2)
Power Supply 12 to 42 Vdc, see Section 4.3.4
Multimeter:
Current
Voltage
Accuracy of at least .05% to check calibration
Range: 4 to 20 mA to measure loop current
Range: 10-40 Vdc to measure power supply and loop voltage
Current Sense Resistor
250 to 1100 to support HART digital communications
Configuration Device Moore XTC Communicator (MXC)
User Configuration Configuration data for transmitter under test
NOTE
Test equipment should be 2 to 10 times more accurate than the desired
transmitter accuracy.