XTC COMMUNICATOR UM344-2
September 1995
2
-
6
2.3 LOOP CONNECTION
The MXC is quickly connected into a transmitter loop. A 40" (1m) cable with a dual banana plug on one
end and two mini-grabber clips on the other is provided. The dual banana plug is inserted into the bottom
of the MXC. The mini-grabber clips are connected to the Model 344's signal terminals or to the loop's
current sense resistor, usually at a receiving instrument such as a Model 352 Single-Loop Digital Controller
(see notes below). This is a non-polar connection. The MXC can now communicate with the transmitter
from the control room or a field location. The diagram below shows a basic loop with the MXC connected
at various locations.
NOTE
The HART protocol requires a network (loop) resistance between
250 and 1100 to support communications. See Section 4.3.5 to
determine resistance value.
IMPORTANT
In a hazardous area installation, connect the MXC on the safe side
of the barrier, between the current sense resistor and the barrier.
MXC
MXC
MXC
Controller,
Recorder,
Indicator,
or other
Device
Notes:
1. Connect an MXC to any of the locations shown.
2. Connect the MXC only in a non-hazardous area.
+
_
Current Sense
Resistor, 250 to
1100 Ohms
+
_
+
_
Signal Test
Model 344
Terminals
X02849S1