Page 96 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FCO1
mmmmm
Modbus Register Types
Usually, the parameters are all read / write.
Each parameter register has a corresponding format register that holds the format
information required to interpret the value. See
Format Words (R46,000 to R46,999)
on
page 98.
Parameter Indexing
Many parameters are indexed. There are two possible indexes: a primary index and a
secondary index. A secondary index is a sub-address of the primary index. Some indexed
parameters affect multiple I/O devices.
The following is an example of a primary index:
P111 is the Relay Control Function. This parameter determines how a relay is controlled
by the HydroRanger 200 (used as an alarm, for pump control, etc.). Because there are six
relays on the HydroRanger 200, P111 is indexed by six to allow each relay to be
programmed independently.
A few parameters also have a secondary index. While a secondary index is important for
setting up the HydroRanger 200, it is almost never needed through remote
communications.
Indexing the Parameter Access Area
Each parameter communicates its value to only one register. You must know the index(es)
for the parameter in order to interpret the information in the register correctly.
For example, to make use of the value returned in register R44,111 you must know which
relay it is referring to. See
Relay Function Codes (P111 Only)
on page 104 for details on
P111 values.
To determine the index values, the primary and secondary index must be read or write.
The two possible methods of handling these index values are described in the following
paragraphs:
Global Index Method
and
Parameter Specific Index Method
.
Reading Parameters
To read parameter values, follow the steps listed in either the Global or the Parameter
Specific Index Method that follow. You must be able to program your HMI or SCADA
system before completing these methods.
Note:
Parameters P000 and P999 are read only. If P000 is set to lock activated then all of
the parameters are read only
Parameter P999 (Master Reset) cannot be used via Modbus
•See
Data Types
on page 101 for a description of the different types of data
associated with different parameters