Page 136 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
mmmmm
Parameters
P137 Pump Group
Puts pumps into groups for multiple pump rotations on one transducer.
This feature groups pumps (relay points 1 - 6) into groups 1 or 2. It is applied to pump
rotation and occurs independently within each group.
Flush Systems (P170 to P173)
Use this feature to control an electrically operated flush valve on a pump to divert some
pump output back into the wet well to stir up sediment.
Standard Mode
Enter the relay number of the pump with the flush valve. The activation of this pump relay
drives the usage of the flush system. Both P172 Flush Interval and P171 Flush Cycles are
based on the operation of this relay and control any relay set to P111 = 64, Flush Valve.
Example:
If you need to watch pump Relay One to control a flush valve on Relay Two you would set
P170[2]=1.
Primary Index Relay
Values
Range: 1 to 2
1 * group 1
2group 2
Alters
P111 Relay Control Function when P111=52 (Alternate duty
assist) or 53 (Alternate duty backup)
Note:
If any of the following parameters are set to 0, this feature will not work.