Keypads
105
Building Technologies
Fire Safety & Security Products
Keypad Tamper Outs
P88E 1-8E 1-8E
If the keypad has a Tamper Switch fitted and this switch is activated, the Tamper
Alarm can be assigned to an output or multiple outputs. This can be used to
operate an audible or visual alarm connected to the output. This function is useful
when the Keypad is installed in a not supervised outside public area.
Option 1 = Output 1; Option 2 = Output 2 etc.
Keypad Error Outs
P89E 1-8E 1-8E
If someone is attempting disarm the alarm by trying various code combinations and
they enter in 4 wrong codes the panel will go into a Wrong Code tamper alarm. The
Alarm can be assigned to an output or multiple outputs. This can be used to
operate an audible or visual alarm connected to the output. A correct code entry
will reset the tamper alarm.
Option 1 = Output 1; Option 2 = Output 2 etc.
Keypad Tamper Beep
P93E 1-8E 1-8E
If someone enters in an incorrect code more than 4 times or a Keypad Tamper
Switch Alarm is generated, the alarm can be silent or it can operate the buzzer in
the keypad. The selected keypad.e.g. P93E 1E for keypad number 1 is the one at
which the alarm has occurred and the options 1-8 are the keypads that will beep in
alarm.
Option 1 = Keypad 1; Option 2 = Keypad 2 etc.
18.12 Keypad chime timer
Keypad Chime Time
P94E 1-8E 0-255E
(Value = 0-255 1/10
th
Second)
When a Chime Zone is activated it can operate an output and/or beep the keypad
buzzer. There is a separate chime timer for each of the 8 keypads. If the value is
made 0 for a keypad the Chime Zone will not beep the keypad buzzer. The Keypad
Chime Timer can be set to a value from 1-255. The units are in 1/10
th
second
increments. This means that a value of 10 will beep the keypad buzzer for 1
second.