Zones
119
Building Technologies
Fire Safety & Security Products
20.9.2 Retrigger time
Zone Lockout Counter
P146E 1-16E 0-255E
(Value 0-255 Minutes)
Each Zone has its own alarm Re-trigger Time. The delay can be programmed from
0-255 minutes. Once a zone has activated it cannot be activated again until the
Re-trigger Time has expired.
20.10 Armed and stay mode entry delay times to output mapping
Zone Entry Output/Away
P161E 1-16E 1-8E
If the alarm is Armed and a delay zone triggers the entry delay it can also beep an
output to warn that the entry delay is counting down and the alarm should be
turned off.
Option 1 = Output 1; Option 2 = Output 2 etc.
Zone Entry Output/Stay
P162E 1-16E 1-8E
If Stay Mode is Armed and a delay zone triggers the entry delay it can also beep
an output to warn that the entry delay is counting down and the alarm should be
turned off.
Option 1 = Output 1; Option 2 = Output 2 etc.
20.11 Zone movement / activity control – watch timer
This option sends a reporting signal to the connected Alarm station if a Zone has
not detected any movement/ activity while disarmed for a certain period. Normally
this option is used to monitor older people by the use of motion detectors and helps
the Alarm center to control if the user is still moving around/ is active.
The wireless motion detectors have a inhibit time (2min.) and do not transmit a signal all the time
when motion is detected. Refer to the Detector description of the used detector.
Zone Activ Time
P163E 1-16E 0-9999E
(Value 0-9999 Minutes)
If the zone is programmed as a Sensor-watch zone (P124E 3E) and it is not
operated within the time set at this location a Sensor-Watch alarm will be
generated. If a detector has this option turned on and it doesn’t operate when
disarmed, this timer will start to count down for the zone/s concerned. The timer is
stopped when the area assigned to the zone/s is armed and resumes with the
saved value when disarmed again. The timer is reset back to the original value
every time the zone operates while disarmed.