Zones
118
Building Technologies
Fire Safety & Security Products
Zone Supervise Beeps
P140E 1-16E 1-8E
If a zone is programmed as a radio zone and that type is actively monitoring the
supervision signal, a supervise signal failure from the detector alarm can sound the
buzzer at selected Keypads for local alarm signaling.
Option 1 = Keypad 1; Option 2 = Keypad 2 etc.
Zone Active Beeps
P141E 1-16E 1-8E
If the zone is programmed for inactivity monitoring (P124E 3E) and it is not
operated within the time set at P163E a Sensor-watch alarm will be generated. A
Sensor-Watch failure from the detector can sound the buzzer at selected Keypads
for local alarm signaling.
Option 1 = Keypad 1; Option 2 = Keypad 2 etc.
Zone Arm Entry Beeps
P142E 1-16E 1-8E
If the alarm is Armed and a delay zone triggers the entry delay it can also beep the
keypad buzzer to warn that the entry delay is counting down and the alarm should
be turned off.
Option 1 = Keypad 1; Option 2 = Keypad 2 etc.
Zone Stay Entry Beeps
P143E 1-16E 1-8E
If Stay Mode is Armed and a Stay Mode delay zone triggers the entry delay it can
also beep the keypad buzzer to warn that the entry delay is counting down and the
alarm should be turned off.
Option 1 = Keypad 1; Option 2 = Keypad 2 etc.
20.9 Zone timing settings
20.9.1 Entry delay time
Zone Arm Entry Time
P144E 1-16E 0-9999E
(Value 0-9999 Seconds)
Each Zone has its own Entry Delay Time when in the Full Armed State. The delay
can be programmed from 0-9999 seconds in one second increments. If the entry
delay is set to 0 the zone will be an instant zone.
Zone Stay Entry Time
P145E 1-16E 0-9999E
(Value 0-9999 Seconds)
Each Zone has its own Entry Delay Time when in Stay Mode. The delay can be
programmed from 0-9999 seconds in one second increments. If the entry delay is
set to 0 the zone will be an instant zone.