Contact ID code summary
143
Building Technologies
Fire Safety & Security Products
26.3 Contact ID code summary
In addition to the programmable Contact ID Event Code assignments defined at
P157E, P158E, P159E, P175E (10E-11E), there are a number of fixed event
codes. The programmable and fixed event codes are all listed in the table below.
Associated with the fixed and programmable event codes, there are a number of
extension codes that are also listed below. The list of extension codes is for your
reference only and can not be changed in programming.
Event Type Event Code Extension Comment
System Tamper 137 000 Panel & Sat Tamper etc
Zone Alarm (wired or wireless) 130 001 to 016 Alarm on Zone 1-16
Zone Tamper - Low (short circuit) 383 001 to 008 Zone Input 1-8 short circuit
Zone Tamper - High (open circuit) 383 009 to 016 Zone Input 1-8 open circuit
Zone Tamper - Radio Zone 383 001 to 016 Radio Zone 1-16
Zone Near Alarm 138 001 to 016 Zone Input 1-16
Zone Confirmed Alarm 139 001 to 016 Zone Input 1-16
Radio PIR / Reed Switch Battery Low 384 001 to 016 Radio Zone 1-16
Radio PIR Supervised Alarm 381 001 to 016 Supervised Radio Zone 1-16
Sensor-watch Alarm 391 001 to 016 Zone 1-16
Zone Excludes 570 001 to 016 Exclude Zone 1-16
Keypad Panic (or 1&3) 120 001 to 008 Panic at keypad #1-8
Radio-Key Panic 120 021 to 100 Panic by Radio User # 21-100
Keypad Fire (4&6) 110 001 to 008 Fire Alarm at keypad #1-8
Keypad Medical (7&9) 100 001 to 008 Medical Alarm at keypad #1-8
Keypad Tamper Switch Alarm 137 101 to 108 Keypad 1-8 Tamper Switch Activated
Wrong Code Alarm 461 001 to 008 4 Incorrect code entries at KP # 1-8
Arm/Disarm by <Arm> key (Quick Arm) 408 000 Arm/Disarm by single button
Arm/Disarm by user code 401 001 to 100 Arm/Disarm by User #1-100
Arm/Disarm by Radio-key 400 021 to 100 Arm/Disarm by Radio User #21-100
Arm/Disarm by Key-switch #1 409 000 Key-switch # 1 Arm/Disarm
Arm/Disarm by Key-switch #2 409 001 Key-switch # 2 Arm/Disarm
Arm/Disarm by DTMF or Up/Download 407 000 Remote Arm/Disarm
Arm/Disarm by Time-Zone 403 000 Time-Zone Arm/Disarm
Latchkey Disarm 642 001 to 100 Latchkey User Disarm
Fail to Arm on Time-Zone 455 000 Auto Arm fail
Delinquency Alarm 454 000 System not Armed within # days
Stay Mode Arm/Disarm (part set) 441 000 Arm by <Stay> Button
Stay Mode Arm/Disarm (part set) 441 001 to 100 Stay Mode Arm by User # 1-100
Stay Mode Arm/Disarm by Key-switch 442 000 Stay Mode Arm by Key-switch # 1
Stay Mode Arm/Disarm by Key-switch 442 001 Stay Mode Arm by Key-switch # 2
System Battery Low 302 000 Control Panel Battery low
Mains Fail 301 000 Mains (AC) fail
Fuse Fail 312 000 Fuse 1 or 2 Fail
Radio-key Battery Low 384 021 to 100 Radio-key User #21-100 low battery
Radio-PIR / Reed Switch Battery Low 384 001 to 016 Radio Zone 1-16
Automatic Test Calls 602 000 24 hour test
Manual Test Calls 601 000 User generated Test Call
Phone Line Failure 351 000 Reported when line is restored
Duress Alarm 121 001 to 008 Duress at Keypad #1-8
Program Modes Accessed 628 001 to 008 Program Mode entered at KP # 1-8
Output 1 or 2 Tamper 323 001 or 002 O/P 1 or 2 wires cut.