Areas
90
Building Technologies
Fire Safety & Security Products
Area B Options
P46E 1-2E 1-8E
(1 = Area A, 2 = Area B)
Option Display text Description
1
Near/Confirm
Reporting
Use Near and Verified Alarm reporting for All zones in this Area: to reduce the
possibility of false alarms the panel can require two alarms on different zones within a
45 minute period before a full alarm will be sent. If this option is turned on it applies to
all zones assigned to that area. An alarm on a single zone will send a Near Alarm
report to the Monitoring Station.
If no further alarms occur within 45 minutes the near alarm timer is reset and a restore
is sent for the zone that activated. If the zone that activated is still in alarm when the
45 minute timer expires, a zone bypass for that zone will be sent and the zone will
remain bypassed until the area is disarmed. Any new alarms after the timer has
expired will send another Near Alarm report. If a second alarm on a different zone
occurs within 45 minutes of the Near Alarm, an Intrusion Verified alarm report will be
sent. This format only applies to Contact ID and Pager reporting. Turning this option
on will stop zone alarms from being reported in Domestic & Voice formats as there
are no messages for near and confirmed alarms. You must turn this option off if using
Domestic or Voice formats
2
Arm at Time
Zone end
Area will Arm at the end of Time Zone: the panel is capable of automatically arming
on a time zone. If this option is turned on and a time zone is selected at P68E, the
Area will automatically arm when the time zone ends. If the panel cannot arm
because it is not Ready, a fail to arm report will be sent.
3
Open at Time
Zone start
Area will Disarm at the end of Time Zone: the panel is capable of automatically
disarming on a time zone. If this option is turned on and a time zone is selected at
P68E, the Area will automatically disarm when the time zone starts.
4
Tags Chirp
Output
Assign Chirps to Access Tags: if the panel is being armed or disarmed by an access
Tag/Card from a proximity reader it is possible to link the pendant chirps programming
(P50E-P53E) to arming or disarming via the access Tag or Card. If this option is on
the chirps will apply to access Tag/Cards. If the chirps are required to be displayed at
the reader LED, the minimum pulse timer for the output (P39E) must be a value of 10.
5
-
Spare
6
-
Spare
-
Up to version 9.07: Spare
7
No Arm on
Violation
Valid as of version 9.07:
Cannot Arm if Zone Unsealed at end of Exit Delay: if this option is turned on and a
zone becomes unsealed as the exit delay expires the panel will fail to arm and report
this via the dialer. The unsealed zone must be corrected and the system re-armed
again.
According EN 50131-3 the system shouldn't Arm if one of the zones is open at the
end of Exit Delay.
8
Spare