Areas
91
Building Technologies
Fire Safety & Security Products
17.2 Area arm-stay pulse and chirps to output
Area Arm Follow
P47E 1-2E 1-8E
(1 = Area A; 2 = Area B)
For monitoring purposes an arm indication can be assigned to an output. Each
Area can have a separate arm indication assigned to a different output if required.
Option 1 = Output 1; Option 2 = Output 2 etc.
Area Stay Follow
P48E 1-2E 1-8E
(1 = Area A; 2 = Area B)
For monitoring purposes a stay arm indication can be assigned to an output. Each
Area can have a separate indication assigned to a different output if required.
Option 1 = Output 1; Option 2 = Output 2 etc.
Area Open Follow
P49E 1-2E 1-8E
(1 = Area A; 2 = Area B)
For monitoring purposes a disarm indication can be assigned to an output. Each
Area can have a separate disarm indication assigned to a different output if
required.
Option 1 = Output 1; Option 2 = Output 2 etc.
Area Arm Chirp
P50E 1-2E 1-8E
(1 = Area A; 2 = Area B)
When arming the alarm using a Radio Key it is necessary to have some form of
Arm indication. This can be done by pulsing an output once when the area is
armed (one chirp). The Chirp is linked to the pulse time (P39E) for the output
concerned. If Output 1 or 2 are used for the chirp and a horn speaker is connected
to the output (see chapter
16.1: Output options; Output D Options, option 1; P37E
1 or 2E), the siren on the output will give a single tone for the chirp instead of the
swept tone used for alarms. Also arming via an access Tag/Card can generate the
chirp if option 4 is on at P47E.
Option 1 = Output 1; Option 2 = Output 2 etc.