System overview
29
Building Technologies
Fire Safety & Security Products
Outputs 1 & 2
Fully programmable, high current, open drain (high-going-low) type FET outputs
capable of switching up to 1 A @ 12 V DC. These 2 outputs are normally set as
switched outputs, providing power for 12 V sirens. If required, these outputs can be
programmed to be siren outputs designed to drive an 8 ohm 10 watt horn speaker
on each output (refer to chapter
16.1: Output options; Output D options, option 1;
P37E). Also if a horn speaker is connected to output #1 you may select (refer to
chapter
22.4: Listen dialing function through keypad and output; Output 1 Listen In;
P175E 7E) as the listen-dialing feature, to listen to the dialing sequence which than
could be heard at the speaker.
In IC60 compact unit the output 1 is assigned to operate the build in internal siren.
Output 3
This is a low current, open drain (high-going-low) type FET outputs capable of
switching up to 500 mA. Like outputs 1 & 2 it is fully programmable.
Connecting devices which draw current in excess of 500 mA to output 3/can
damage the output.
Output 4-Relay Out
Output 4 is a relay output with single pole changeover contacts. If required, the
Common (C) contact of the relay is connected by default to GND via JUMPER, the
jumper can be selected to 12 V or removed.
4.6 System Bus connection - keypad port
The terminals marked POS, NEG, CLOCK, & DATA make up the communications
port which the keypads and other intelligent bus devices use to communicate with
the Sintony 60. The terminals are connected to corresponding terminals on the
remote devices. The LIN terminal is only used by the keypads and utilizes a fifth
wire to provide a communicator listen-dialing facility (a dialing ton could be heard
through the buzzer). This feature is particularly useful when servicing monitoring
faults. The 12 V power supply (POS, NEG) of the bus is protected by a separate
thermal fuse.
4.7 Programming port
With the separate available programming cable IAQ6-1 and the programming
software Sylcom 60 IAS6-1 the Sintony 60 could be connected via this port directly
to a PC. All system parameters or settings could be easily changed with this
program. Furthermore this port could also be used to connect the memory stick
IMM6-10 to up or download the default setting of an alarm system. This speeds up
the process of programming, especially if similar settings have to be used with
different installations.
If the control panel is connected to the telephone line, the same software could be used to program/
monitor the control panel through the telephone line remotely, if the PC is equipped with a telephone
modem.