09.91 11 Alarms
11.7 RS232C (V.24) Alarms
Cause:
Remedy:
31
No free PP number RS232C (V.24)
The maximum number of programs specified by means of
machine data has been reached.
• Erase old programs and reorganize memory
• Modify MD 8 and reformat part program memory
Sequence:
a. ”SET UP OVERALL RESET” mode
b. ”FORMAT USER MEM.” softkey
c. ”CLEAR PARTPR.” softkey
Old programs are then deleted!!
Cause:
Effect:
Remedy:
• Permissible number of decades after an address is incorrect
• Decimal point in wrong position
• Part programs or subroutines are not correctly defined or
terminated (observe pre-header!)
• NC expects a ”=” character, but this character is not defined
in EIA code
Data transmission interrupted
Last block not stored
Check data to be read in
32
Data format error RS232C (V.24)
Different programs same number RS232C (V.24)
Read-in and stored programs not identical for same
program number
Wrong program number in BTR mode.
No data stored
Delete old program or
rename old program with ”RENAME”
If an existing program with the same program number is
read in again, the two programs are compared.
If they differ,
Alarm 33 is activated.
If in BTR mode a program number 0 is preselected in the NC and a
program with another program number is offered from outside via the
serial interface, then Alarm 33 is given.
33
Cause:
Effect:
Remedy:
Explanation:
© Siemens AG 1990 All Rights Reserved 6ZB5 410-0DL02 11–15
SINUMERIK 810 GA3/820 GA3 (IA)