Cabling and Wiring the System
SIMATIC 545/555/575 System Manual
4. Strip back 1.50 in. (38 mm) of the sleeving on the other end of the
cable.
5. Remove 0.13 in. (3.3 mm) of each color-coded insulation to expose the
bare wires.
6. Install each wire end onto a terminal lug according to directions
provided by the vendor.
The size of the terminal lug depends on the type of terminal block used.
Consult your vendor for the appropriate terminal lug size.
Figure 6-6 shows the pinout for the I/O Link port on Series 505 CPUs and
RBCs. The I/O Link port is a 9-pin, female D-connector.
Ground (5)
TX/RX+ (3)
TX/RX (8)
6
1
9
5
Figure 6-6 I/O Link Pinout
Remote I/O Port
Pinout