Troubleshooting
9-10
SIMATIC 545/555/575 System Manual
Troubleshooting CPU Fatal Errors (continued)
The following is a list of the 575 fatal errors:
• Board table, system descriptor table, or application table mismatch —
these tables do not match the power-down configuration on the next
BATTERY GOOD powerup.
• The configuration switches are inconsistent.
• VMEbus error — the CPU receives a bus error while attempting to
access a VMEbus address, and you have not indicated that such errors
should be ignored.
NOTE: Release 3.0 and later provide recovery from VMEbus errors if the
MOVE or XSUB instruction initiates the bus transaction. Refer to the
SIMATIC 545/555/575 Programming Reference User Manual for details.
Table 9-5 describes AUX 29 fatal error codes.
Table 9-5 Aux 29 Fatal Error Codes
Code Description
0001 Error creating the boot task
0002 Intertask message logic error
0003 Illegal interrupt
0005 Invalid SFOS service call code
0006 Task queue logic error
0007 Stack error
0008 Heap logic error
0009 Heap overflow
000B Lock/sema logic error
000D Task management logic error
0011 Timer list processing logic error
0016 Specified task not an IOCT
0017 Incompatible task attributes
0022 Dispatcher flags (DSPFLG) have been corrupted
0023 IOCB table is full
0024 I/O already in progress
0025 Uninitialized I/O
0026 I/O processing logic error
0027 Invalid system stack pointer
0028 Invalid user stack pointer
0029 Total queue size is invalid
575 Fatal Errors
545/555/575 CPU
Fatal Error Codes