Troubleshooting
9-4
SIMATIC 545/555/575 System Manual
Troubleshooting by Using Auxiliary Functions (continued)
AUX 17 (Compare PLC to Disk) compares the selected program on disk to
data in the CPU.
AUX 20 (PLC Diagnostics), available only for 545/555 CPUs, initiates the
CPU self-checks. The CPU must be in PROGRAM mode in order to execute
self-tests. For 545/555s, the CPU executes the equivalent of an AUX 20 at
every powerup. If any area fails, a message detailing the failure is
displayed. AUX 20 makes the following tests.
• Valid RAM locations are verified.
• Pre-coded ROM checksum values are checked.
• The hardware force function is checked.
• Internal timer operation is verified.
AUX 25 (Display Failed I/O) displays the locations of any failed I/O modules
that are capable of diagnosing and indicating failure. Some modules, such
as word and analog modules, report that they have failed if the
user-supplied voltage is not correct.
AUX 25 also displays I/O mismatch(es), indicating that one or more
installed module(s) do not agree with the I/O configuration. Verify that the
configuration data for listed modules is correct before considering that the
module may actually be malfunctioning.
AUX 29 (PLC Operational Status) checks the operational status of the CPU
and displays the results. The display provides the information illustrated in
Figure 9-1. Field descriptions are listed below.
• Application ID (575 only) Identifies the CPU currently selected.
• Communications Identifies port or network in use.
If you are using a communications port, the port is identified, followed
by a space and the protocol: e.g., P1 TBP, or P2 NITP. The current baud
rate is displayed in a field to the right.
If you are using a network, the network is identified: e.g., TIWAY
NETWORK, or H1 NETWORK. In the case of H1, the network
connection name is displayed, in quotation marks, in a field to the
right.
• Scan Scan time reported by AUX 29; it is the highest scan time
recorded since the last CPU reset, PROGRAM–RUN mode transition,
or user peak resets. Status Word 10 (STW10) contains a continuously
updated report of the scan time.
Compare PLC
to Disk
Run 545/555 PLC
Diagnostics
Display Failed I/O
PLC Operational
Status