Siemens SIMATIC TI500 Spezifikationen Seite 302

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 322
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 301
575 I/O Module Specification & Pinouts
E-13
SIMATIC 545/555/575 System Manual
Table E-11 shows the module specifications, and Figure E-6 shows the effect
that temperature has on current output, for the PPX:5754732.
Table E-11 PPX:5754732 Specifications
Feature Description
Optical isolation 1500 Vrms
Isolation between commons 500 Vrms
Isolation between chassis ground and
user circuits
1000 Vrms
Outputs 32
Commons 4
Fuses
One 8 A, 125 V normal-blow, 5 x 20 mm
fuse per common (4 fuses total).
Replace only with UL/CSA-listed fuse.
Output type Non-latching, unprotected
Operating voltage range 4.5 to 36 VDC
Maximum off-state leakage current 0.2 mA
Maximum on-state voltage drop 2.2 VDC
Minimum load current per point 1.0 mA @ 24 VDC
Maximum delay time through module
(with 5 mA load)
2 ms, on to off;
2 ms, off to on
Inductive load kickback Diode protected
Temporary overload 5.0 A for 1 ms
+5 V base current consumption 1.0 A maximum
User power current (with no load) 3.0 mA maximum per common
0.0
0.5
1.0
1.5
2.0
0 10203040506070
With fan cooling Without fan cooling
Current (A)
Current (A)
Temperature (°C) Temperature (°C)
0.0
0.5
1.0
1.5
2.0
0 10203040506070
4 on
8 on
16 on
32 on
1 on
4 on
16 on
32 on
Figure E-6 PPX:5754732: Current/Point vs. Ambient Temp
Seitenansicht 301
1 2 ... 297 298 299 300 301 302 303 304 305 306 307 ... 321 322

Kommentare zu diesen Handbüchern

Keine Kommentare