Upgrading Existing Series 500 Installations
C-14
SIMATIC 545/555/575 System Manual
Installing a PPX:500–5114–A RBC (continued)
When I/O channel communication to a base is lost, the state of the outputs
is determined by the selection made on the RBC (Off/Freeze) switch. See
Figure C-6.
FREEZE
OFF
(factory set)
Figure C-6 Series 500 RBC Switch Selection
For discrete output modules, the state of the outputs is determined solely by
the position of the RBC (Off/Freeze) switch.
For analog/word output modules, the state of the outputs is influenced not
only by the position of the RBC (Off/Freeze) switch but by the output
module’s (Zero/Hold Last Value) selection, if the module has that option. See
Table C-1.
Output State
Selection