4.5 Installing the Fan Assembly
You can operate the PPX:575–2130 base with the fan assembly at standard
rated power of each I/O module and the power supply at any ambient
temperature up to 60°C. Refer to Appendix E for I/O module derating charts
with and without forced air flow.
Table 4-1 lists the requirements that apply when you set up your system
without the fan assembly.
Table 4-1 Derating Requirements for Operation without Fan Assembly
Module
Derating @ 40°C w/o Fans
PPX:575–6660 185-watt power supply
1
60 watts maximum power load
PPX:575–6663 300-watt power supply 100 watts maximum power load
575 I/O modules Refer to Appendix E for I/O module
derating charts without forced air
flow.
Other vendor’s VME modules Refer to vendor’s specifications for
operating requirements without
forced air flow.
1
For use without fans, power supply PPX:575–6660 must have manufacturer date
after 2/94. You can verify this by ensuring that the Prodok revision label is
marked with numeral 3 or higher, as shown here:
12345
678910
To install the fan assembly, you must perform three tasks: select the correct
voltage, connect power to the AC terminals, and mount the assembly.
Because the voltage selector switch and AC terminals are located at the rear
of the unit (see Figure 4-1), you should set the voltage selection and connect
power before mounting the fan assembly.
Operating With
Fan Assembly
Operating Without
Fan Assembly
Installation
Sequence