Troubleshooting
9-3
SIMATIC 545/555/575 System Manual
Table 9-1 shows the effects of using AUX 10, AUX 11, and AUX 12.
Table 9-1 Effects of Using AUX 10, AUX 11, and AUX 12
Power-up Restart Partial Restart Complete Restart
AUX 10 AUX 11 AUX 12
Battery Battery Battery
System Characteristic ON OFF ON OFF ON OFF
CPU Mode (RUN, PGM,
HOLD, RAM, ROM)
No
change
1
Program
2
No
change
3
No
change
3
No change
3
No change
3
Loop Processing Mode No change
Program/
LOCK
2
No
change
3
No
change
3
No change
3
No change
3
Loop Mode No change N/A No change No change Manual Manual
Discrete I/O (Xs and Ys) Cleared Cleared Cleared Cleared Cleared Cleared
Word I/O
(WXs and WYs)
No change Cleared No change No change Cleared Cleared
Non-Retentive
Control Relays
Cleared Cleared Cleared Cleared Cleared Cleared
Retentive Control Relays No change Cleared No change No change Cleared Cleared
Forced Elements No change Cleared No change No change No change No change
TMR/CTR/Drum Presets No change Cleared No change No change Downloaded Downloaded
L, V, K, S, U Memory No change Cleared No change No change No change No change
Memory Configuration No change Default value No change No change No change No change
I/O Configuration No change Cleared No change No change No change No change
DP I/O Mode No change STOP No change No change No change No change
DP Sync Mode No change Async No change No change No change No change
Scan Time No change Variable No change No change No change No change
Time of Day No change No change No change No change No change No change
Task Codes/Scan No change 2 No change No change No change No change
Watchdog Value No change 1 sec No change No change No change No change
Port Lockout No change Unlocked No change No change No change No change
Fatal Error No change Cleared Cleared Cleared Cleared Cleared
1 If in EDIT mode, Go to PROGRAM mode prior to RUN mode.
2 For 545/555 CPUs: if programmed (E)EPROM is present, then RUN mode using program in (E)EPROM.
3 If fatal error was present, then PROGRAM mode.